In this article we discuss how
to calculate the power flow in symmetrical components. Symmetrical components
are balanced three-phase vectors derived from the unbalanced phase vectors in a
three phase electric system.
In any 3-phase electric
system, if there is an unbalanced vector (whether representing voltages or
current), it can be resolved into three balanced systems of vectors which are
known as its symmetrical components.
By using this we are able to
solve any polyphase (usually 3-phase)
circuits having unbalanced vectors for:
○ Finding the performance of polyphase electrical machinery when it is operated
from a system of unbalanced voltages.
○ Calculation of currents resulting from
unbalanced faults in the system.
Power flow calculation in symmetrical
components solutions is nothing but a voltage and current flow calculation in
an unbalanced 3-phase system.
Now let us take an unbalanced
3-phase system which three unbalanced voltage vectors Va, Vb, Vc having phase
sequence a-b-c.
The above vectors can be
resolved
into:
○ A balanced system of 3-phase vectors Va1,
Vb1, Vc1 having the phase sequence a-b-c, and this is same as that as the
original set of three unbalanced vectors, so this is called positive sequence
components.
○ A balanced system of 3-phase vectors Va2,
Vb2, andVc2. The phase sequence of these vectors a-c-b is opposite to that of
the original unbalanced vectors, and this is known as negative sequence
components.
○ A balanced system of three vectors Va3,
Vb3, and Vc3. All these vectors are equal in magnitude and are in phase with
each other Va3=Vb3 =Vc3s so this is known as zero sequence components.
Therefore it has been seen
above that an unbalanced 3-phase system of voltages or currents can be regarded
as due to two symmetrical 3-phase systems having opposite phase sequence and a
system of zero phase sequence.
The resultant vectors, which
we get after combining positive sequence vectors and negative sequence vectors,
are shown below:
Va = Va1 + Va2 + Va3 ------- (equation
1)
Vb = Vb1 + Vb2 + Vb3-------- (equation
2)
Vc = Vc1 + Vc2 + Vc3 --------
(equation 3)
In the above equation, the
suffix 1 indicates that the vector belongs to the positive –sequence components
and a vector with suffix 2 indicates the vector belongs to the negative-
sequence components. Also a vector with suffix 0 indicates that the vector
belong to the zero-sequence components.
Usually, these vectors are
related to each other with the help of the operator e.
The positive sequence vectors
have phase sequence a-b-c and hence they are related as:
Va1 = Va1
Vb1 = e2 Va1
Vc1 = e Va1
The negative sequence vector
have phase sequence a-c-b and hence the vectors are related as:
Va2 = Va2
Vc2 = e2 Va2
Vb2 = e Va2
The zero sequence vectors are
in phase with each other and have the same magnitude, and hence they are
related as:
Va3 = Vb3 =Vc3
Therefore substituting the
above in equation 1, 2, and 3 we get
Va = Va1 +Va2 +V3
Vb = e2 Va1 + eVa2 +V3
Vc = e Va1 + e2 Va2 +V3
For our convenience, let us
write Va1 as V1, Va2 as V2.
Va =V1+ V2 + V3 ----------- (equation4)
Vb = e2V1 + eV2 + V3 -----------
(equation5)
Vc = e V1+ e2V2 +V3 -----------
(equation6)
An unbalanced 3-phase current
can also be similarly linked into its symmetrical component.
Ia =I1 + I2 + I3 -------- (equation7)
Ib = e2 I1 + e I2 + I3----------
(equation8)
Ic = e I1+ e2 I2 + I3---------
(equation9)
Estimation of Power Flow or
Voltage and Current Flow in Symmetrical Components
Estimation of V1 and I1
From equation 8 and equation 9
We can have
e Ib =
e3 I1 + e2 I2 + e I3
e2 Ic =
e3 I1 + e4 I2 + e2 I3
Now let us assume that e3 =1
and e4 = e
e Ib= I1 +
e2 I2 + e I3---------- (equation 10)
e2 Ic =
I1 + e I2 + e2 I3------------(equation 11)
By adding equation 7,
equation10, equation11 we get
Ia +e Ib +e2 Ic = I1 +I1 +I2 + I2 + e2 I2 + e I2 + I3 + e I3 +e2 I3
Ia +e Ib +e2 Ic = 2 I1 + I2 ( 1+e+e2)
+ I3 (1+e+e2)
Ia +e Ib +e2 Ic = 3 I1
I1= 1/3 (Ia +e Ib +e2 Ic)
The same can be applied for V1
V1 = 1/3(Va +e Vb +e2 Vc)
Similarly applying the above
methods V2 or I2 and V3 or I3 can be calculated.
V2 = 1/3(Va +e2 Vb + e Vc) and I2 =
1/3(Ia +e2 Ib +
e Ic)
V3 = 1/3 (Ia +Ib+Ic) and I3 = 1/3 (Ia +Ib+ Ic)
As we know that power is a
product of voltage and current, the power flow can be calculated by using the
above relations of vectors and currents.
Power =V1*I1 + V2*I2 +v3*I3
It is clear that the I3 and V3
is one third of the neutral or earth return current or voltage and this will be
zero in the unearthed 3-wire electrical system, and also if the vector sum of
the current or voltage vectors is zero, then I3 or V3 will be zero.
If there is a flow of positive
sequence current components, then there is a flow of negative sequence current,
and this is because both are similar, but in case of zero sequence components
to flow, then a fourth wire is necessary in the system... so a set of
unbalanced 3-phase line to line voltages may be represented by a positive and a
negative sequence system of balanced voltages, which are known as symmetrical
components.