Control Valves and Control Stations

Control of flow of process and utility streams is achieved with the help of a control valve. Input to control valve is provided by a sensing device which measures the process parameter to be controlled like Level,

Temperature, Flow, Pressure etc. Sensing devices send their input first to microprocessors which then converts it to appropriate signal to control valve.

Body of the control valve is mostly similar to conventional globe valve. It can be flanged, Socket Welded, Buttwelded, Screwed etc. depending on the applicable piping material specification. Instead of a operator like handwheel, they have a diaphragm actuator which operates on pneumatic pressure. Some control valves are specified for both manual and automatic operation. In such case, they are equipped with a handwheel as well as a diaphragm actuator.

Control Station                                                                                              

1.    Control valves are located as single items in piping systems or are furnished with up and downstream block valves and a bypass valve. These multi-valve arrangements are called control stations.

2.    The blocks and bypass valves are used so that the system can continue to operate during maintenance work on the control valve.

3.    In the most common control valve arrangement, the block valves are located in the vertical section of the assembly, with the control and bypass valve in the horizontal section.

4.    The globe valve can be used to regulate line flow manually while the control valve is out of service.

5.    For other arrangements (e.g. for steam control valve station), the upstream bloc valve is also located in horizontal leg of the piping to accommodate adequate condensate removal.

6.    Low point drains and trunion based supports are also furnished at control valve stations.

Locating Control Stations

1.    Control valve stations are preferably located at grade for the inline unit and at main operating levels for the vertical arrangements.

2.    It is not absolutely necessary to locate control valve stations in such a way that pneumatic or electrical interconnections are kept to a minimum; however, usually, the control valve is located in the same area as its source of control – for example, to facilitate the connection between the vessel level controller and its associated control valve.

3.    The prime considerations, however, are cost and for the more expensive piping systems, accessibility.

4.    Control valve stations are located within process areas for ease of operation and maintenance, preferably on either side of the access aisles, adjacent to equipment and structural columns.

5.    When locating control valves with valve positioners, the plant layout designer must allow adequate clearance between structural columns and vessels.

6.    In case of fail to open valve, only one drain upstream of control valve is required.

7.    In Case of Fail to Close valve, two drains on both sides of control valve are required.

Control Valves Piping Layout

Control valves, block and by-pass valves shall be sized on the PID. Control valves shall be accessible from grade or platforms unless otherwise approved for good process or economic reasons on an individual item basis.

Control valves shall be located in sight of instruments or indicators showing the variables they control. Unless otherwise approved by Owner, control valves shall be located high enough to permit valve stem removal, but not higher than 900 mm above grade or platform.

Where vaporization occurs in control valves, they shall be placed as close as practical to the destination of the stream. Control valve bypass piping shall provide sufficient clearance for the removal of the control valve from the loop.

All control valves shall be provided with block valves and bypass valves rated for the same design pressure as the upstream piping. Bypass valves shall be designed for a capacity at least equal to the capacity of the control valve. Flanged spools shall be used between flanged control valves and block valves.  The length of the spools shall be sufficient to permit removal of bolts and the installation of drain or vent connections.

Valved 3/4″ drains shall be provided on the isolatable spool upstream of control valves.

All control valves in socket weld piping shall be flanged. The only devices which may be mounted on control valves shall be valve positioners, volume boosters, lock-up relays and pressure controllers. These devices shall be installed so as to be easily accessible for servicing. These devices shall not be mounted when vibration may cause malfunction.