Governing Equation for Sensible Heating and Cooling
Example
Calculate the amount of sensible heat that must be added to 100lb of air at 85°F dry bulb and 75°F wet bulb to raise the temperature of air to 100°F dry bulb.
Solution
a) Locate the 85°F dry bulb and 75°F wet bulb – this corresponds to 62% Relative humidity.
b) Move from point established in a) above to right to 100°F on a horizontal dry bulb temperature scale – this corresponds to 39.6% Relative humidity.
The condition of the air is changing from state 1 to state 2
c) Read h2 and h1
• h2 = 39 Btu’s/lb dry air
• h1= 43.5 Btu’s/lb dry air d) Estimate heat addition : Q = m [h2 – h1]
• Q = 10 x [43.5 – 39]
• Q = 10 x 4.5
• Q = 450 Btu’s