Voltage and current levels in electrical engineering is very important. As any electrical system, equipment, devices all are characterized by their different voltage and current levels.
Two types of voltage levels-
· Rated voltage designated for a system or equipment.
· Rated voltage referring to some operating characteristics.
Say for a single phase
motor the designated voltage is 220 volt as it is connected to a phase and a
neutral; for a three phase motor which is connected to three phases the
designated voltageis400V.
Now say for a protection system to be active, the energizing voltage has to be
maintained within 10V to 20V DC- this is an operating characteristics. So 10V,
20V is also a nominal voltage levels.
· Voltage by consideration of the insulation.
· Highest voltage defined by the manufacturer or recommended by the manufacturer.
Electrical system
insulation designed as per the voltage. So the highest voltage level will be
the voltage which the system insulation can sustain.
Also the manufacturer defines some voltage restrictions for a certain
electrical system or equipment. These all are highest voltage levels. Say an
electrical system insulation highest voltage level is 11KV, but the connected
electrical equipment highest voltage level is 5KV, as recommended by the manufacturer.
The definition
of Circuit Breaker: A circuit breaker is an electrical device that is capable
of break or make current in both the normal or abnormal (faulty) condition.
Make
current: is closing the circuit breaker or establishing a
connection. While closing the breaker there is high instantaneous non-linear
current appears for short duration and the electrical system or equipment has
to sustain this.
Break
current is opening the circuit breaker or dis-engaging an
electrical connection. This breaking current might be for normal operation or
might be for abnormal/ faulty condition. While breaking current there is some
time delay and the electrical system or equipment have to withstand high value
of fault current during this short time.
If there is delay in breaking a connection while a fault occurred, the circuit
breaker contacts might become welded by arc and large amount of heat.
– R.M.S value of a current that the electrical system or equipment can carry continuously. This is a normal operating current.
RMS value of a current that an electrical system or equipment can carry in closed position for a specified short duration such as 1s or 3s.
First major loop of the
rated short time withstand current which an electrical system or equipment can
carry in closed position.
For high voltage system rated peak withstand current is 2.5 times of rated
short time withstand current.
For low voltage system rated peak with stand current is 1.5 to 2 times of rated
short time withstand current.
rms value of maximum
symmetrical short-circuit current in KA, which a circuit breaker shall be
capable of breaking.
There are two values included in the rated short circuit breaking current-
· RMS value of the ac component.
· The percentage of DC component.
The maximum peak current
the circuit breaker shall be able to close and latch again. This peak value is
related to the RMS value of the rated short circuit breaking current, frequency
and time constant.
As per ANSI/IEEE rated short circuit making current is also referred to as
closing and latching capability.
Some specified value of rated short circuit breaking current are
If Rated short circuit making current=Ism and rated short circuit breaking current=Isb
· Ism=2.5*Isb, At 50Hz and t=45 ms,
· Ism=-2.6*Isb, at 60Hz, t=45ms.
· Ism=-2.7*Isb, at both 50Hz and 60Hz, t=45ms.