Output Equations and Main Dimensions- Design of Transformers

Single phase core type transformer, Three phase core type transformer

 

:

Description: http://www.brainkart.com/media/extra/yuyc9Y2.webp

Description: http://www.brainkart.com/media/extra/ktQBMCM.webp

Description: http://www.brainkart.com/media/extra/SDmQehT.webp

 

Unless otherwise specified, LV winding is always placed next to the core and HV winding over the LV winding in order to reduce the quantity of insulation used, avoid the possibility of breakdown of  the space between the core and HV coil in case HV coil is provided next to the core and to control the leakage reactance. However in case of transformers where the voltage rating is less, LV and HV windings can be arranged in any manner.

 

SPECIFICATION

 1. Output-kVA

2. Voltage-V1/V2 with or without tap changers and tapings

3. Frequency-f Hz

4. Number of phases – One or three

5. Rating – Continuous or short time

6. Cooling – Natural or forced

7. Type – Core or shell, power or distribution

8. Type of winding connection in case of 3 phase transformers – star-star, star-delta, delta-delta,  delta-star with or without grounded neutral

9. Efficiency, per unit impedance, location (i.e., indoor, pole or platform mounting etc.), temperature rise etc.,

 SIZE OF THE TRANSFORMER

As the iron area of the leg Ai  and the window area Aw = (height of the window Hw x Width of the window Ww) increases the size of the transformer also increases. The size of the transformer increases as  the output of the transformer increases.

 Description: http://www.brainkart.com/media/extra/d0tI1NP.webp

 

NOTE:

Nomenclature:

V1 – Applied primary voltage

V2 – Secondary terminal voltage

E1, E2 – EMF induced in the primary and secondary windings per phase in case of 3 phase

T1, T2 – Number of primary and secondary turns per phase in case of 3 phase

I1, I2 – Primary and Secondary currents per phase in case of 3 phase

a1, a2 – Cross-sectional area of the primary and secondary winding conductors

δ - Current density in the transformer conductor. Assumed to be same for both LV and HV  winding.

φm – Maximum value of the (mutual or useful) flux in weber = AiBm

Bm – Maximum value of the flux density = φm / Ai

Ai – Net iron area of the core or leg or limb = KiAg

Ki – Iron or stacking factor = 0.9 approximately

Ag – Gross area of the core

Description: http://www.brainkart.com/media/extra/flxiMmr.webp

a. It is clear that V1I1 = V2I2 or volt-ampere input is equal to volt-ampere output or kVA rating of both

primary and secondary windings is same.

b. It is clear that I1T1 = I2T2 or primary mmf is equal to secondary mmf.

c. It is clear that E1/T1 = E2/T2 or volt/turn of both primary and secondary is same.

 

Output Equations

 Single phase core type transformer

Rating of the transformer in kVA = V1I1 x 10-3 = E1I1 x 10-3 = 4.44 φm f T1 x I1 x 10-3----(1)

 

Description: http://www.brainkart.com/media/extra/XGXQU2z.webp

Description: http://www.brainkart.com/media/extra/NJ0hHVv.webp

 

Single phase shell type transformer 

Description: http://www.brainkart.com/media/extra/S3RRJtc.webp

Note : Since there are two windows, it is sufficient to design one of the two windows as both the windows are symmetrical. Since the LV and HV windings are placed on the central leg, each window accommodates T1 and T2 turns of both primary and secondary windings.

 

Area of copper in the window

Description: http://www.brainkart.com/media/extra/HkYGSo0.webp

Three phase core type transformer 

Rating of the transformer in kVA = V1I1 x 10-3 = E1I1 x 10-3 = 3 x 4.44 φm f T1 x I1 x 10-3…(1)

Description: http://www.brainkart.com/media/extra/8zV17Wr.webp

Note: Since there are two windows, it is sufficient to design one of the two windows, as both the windows are symmetrical. Since each leg carries the LV &HV windings of one phase, each window carry the LV & HV windings of two phases

Since each window carries the windings of two phases, area of copper in the window, say due to R & Y phases

Description: http://www.brainkart.com/media/extra/IcTabob.webp

 

Three phase shell type transformer 

Description: http://www.brainkart.com/media/extra/H53R9yI.webp



[ Note: Since there are six windows, it is sufficient to design one of the six windows, as all the windows are symmetrical. Since each central leg carries the LV and HV windings of one phase, each window carries windings of only one phase.] 

Since each window carries LV and HV windings of only one phase, 

 

 

Description: http://www.brainkart.com/media/extra/QHmxpnG.webp

 

 

 

 

Description: http://www.brainkart.com/media/extra/ZxDp6wi.webp

Description: http://www.brainkart.com/media/extra/1vmTsfV.webp

 

Description: http://www.brainkart.com/media/extra/qGd2WHN.webp